background image

IP Video Surveillance System

Installation Guidelines

for Endura

® 

Equipment

C2670M-C (9/09)

Содержание DAS5200 Series

Страница 1: ...IP Video Surveillance System Installation Guidelines for Endura Equipment C2670M C 9 09...

Страница 2: ...POWER QUALITY 5 GROUNDING 7 ELECTROSTATIC DISCHARGE PREVENTION 8 ENVIRONMENTAL GUILDELINES 9 ENVIRONMENTAL ELEMENTS 9 OPERATING TEMPERATURE 10 HEATING VENTILATION and AIR CONDITIONING HVAC 12 NETWORKI...

Страница 3: ...be used for all servers As hard disk drive reliability is negatively impacted by temperature extremes care must be taken to ensure that hard disk drives are never exposed to elevated operating temper...

Страница 4: ...r Endura equipment Consult applicable regulations and standards for determining the proper wire gauge to use Generally you should install circuit breakers that are rated at 125 percent of the expected...

Страница 5: ...tage or overvoltage for up to a few nanoseconds Under voltage brownout Low line voltages for an extended period of time NOTE If these issues are suspected or known to occur for a given site ensure tha...

Страница 6: ...alculate the UPS size required for an installation with two NSM5200s connected to the same UPS Example Two NSM5200s are to be connected to the same UPS From Table A each NSM5200 dissipates 262 W of po...

Страница 7: ...in each rack Any reading above 1 V measured between grounds should be considered a problem and investigated Grounding Guidelines Main building electrical ground The main electrical service entrance eq...

Страница 8: ...500 V 14 800 V Source B A Unger Electrostatic Discharge Failures of Semiconductor Devices Bell Laboratories 1981 For the same relative humidity level a high rate of airflow produces higher static char...

Страница 9: ...ees working in the room SITE CLEANLINESS It is critical that the installation site be completely clean and devoid of dust and debris created during the construction process Operation of the equipment...

Страница 10: ...ne an extensive amount of design and engineering to keep the operating temperature of internal components as close to the ambient temperature of the room as possible As such maintaining the right ambi...

Страница 11: ...rflow 274 Video Encoder NET5308T EXP 50 to 95 F 10 to 35 C Front to rear airflow 137 Video Encoder ENC5308 50 to 95 F 10 to 35 C Front to rear airflow 137 Video Encoder ENC5316 50 to 95 F 10 to 35 C F...

Страница 12: ...ool air in through the front of the unit and exhaust heated air out of the back of the unit The ideal server room configuration utilizes cold and hot aisles HVAC vents placed either in the floor or th...

Страница 13: ...t Endura Design Certification and collaborates with select switch vendors If additional assistance is required Pelco offers professional services for the Endura certified integrator CABLING All networ...

Страница 14: ...e system manager is built upon a standard server platform it will suffer drift over time To maintain an accurate time for the entire system Pelco recommends pointing the Endura system to either the NT...

Страница 15: ...ailable 100 percent of the time and the environmental conditions of the equipment location must be maintained within specification WARNING If either conditioned power or the environmental conditions o...

Страница 16: ...n factors that may be helpful in determining those factors required for site planning Refrigeration 1 W 0 86 kcal h 1 W 3 412 BTU H 1 W 2 843 x 10 4 tons 1 ton 200 BTU minute 1 ton 12 000 BTU H 1 ton...

Страница 17: ...party or product liability relating to the Products shall not exceed the price paid by the Dealer to Pelco for such Products In no event will Pelco be liable for any special incidental or consequenti...