Fieldgate configuration
WirelessHART Fieldgate SWG70
54
E Hauser
HART parameters
8.4.4
AMS via Ethernet
If you would like to integrate Fieldgate SWG70 into Emerson’s Asset Management System
(AMS), this must be done via an Ethernet port. In rare cases you will need to change the port
number. The default port setting is "33333".
1. Click
Wired Communication => Protocols => AMS
.
Parameter
Meaning
Default
Bus Address Selection Specifies whether hardware (DIP switch 0–3) or software bus address
settings are to be used
• DIP switch: 0 –15
• Software: 0 –63
Software
Bus Address
Sets the HART address of the wireless fieldgate when
Bus Address
Selection
is set to Software
– When DIP-Switch is selected, displays the setting
1
Baud Rate Selection
Specifies whether hardware (DIP switch 4–5) or software baudrate
settings are to be used
• DIP switch: 9600 Bit/s –57600 Bit/s
• Software: 1200 Bit/s –115200 Bit/s
Software
Baud Rate
Sets the baudrate of the wireless fieldgate when Baud Rate Selection is set
to Software
– When DIP-Switch is selected, displays the setting
19200
Port Number
Sets the Fieldgate SWG70 Ethernet port number for HART via UDP/TCP
transmission
– If the port number is changed, the default port remains open
– HART UDP allows access for two primary masters and two secondary
masters
– HART TCP allows access for one primary masters and one secondary
master
5094