Fieldgate configuration
WirelessHART Fieldgate SWG70
50
E Hauser
8.3
Interfaces (wired communication)
All Fieldgate SWG70 versions feature an Ethernet interface and a serial interface.
Depending on the device version, this interface can support different protocols.
See this section for information about the interfaces. For information about the protocols,
see Chapter 8.4 "Protocols (wired communication)" on page 52.
8.3.1
Ethernet
The parameters contained in this leaf pertain to the set up of the communication to the host
via Ethernet interface offered by Fieldgate SWG70.
1. Click
Wired Communication => Interfaces => Ethernet
to display the associated
parameters:
2. Enter the parameters, pressing
Enter
after each change.
– Note: Automatic IP address assignment requires that there is a DHCP server in the
Ethernet network.
3. Press the
Write Ethernet Information
button when all parameters have been
changed.
– The Fieldgate will restart with the new parameters.
– If the IP address was changed, communication will be lost.
– Change your computer's address if necessary and re-establish communication with
the new IP address.
– If you are using the HART IP CommDTM, reconfigure the communication parameters,
before making connection again. See Chapter 7.3.2 "Adding the Fieldgate SWG70" on
page 38, Step 4.
Fieldgate
SWG70 version
Interface
Protocol
Modbus
EtherNet/IP
HART
AMS
SWG70-xx-1
Modbus
Ethernet
X
–
X
X
Serial (RS-485)
X
–
X
–
SWG70-xx-2
OPC
Ethernet
X
–
X
X
Serial (RS-485)
X
–
X
–
SWG70-xx-3
EtherNet/IP
Ethernet
–
X
X
X
Serial (RS-485)
–
–
X
–