WirelessHART Fieldgate SWG70
Commissioning
E Hauser
41
7.3.5
Scanning for devices connected to adapters
It is also possible to scan for the devices connected to the adapters. Depending on the size of
the network and the connected field devices, however, it is possible that time out problems
occur. In this case, FieldCare issues a warning and the user can choose to cut the connection,
wait for connection or retry the connection.
1. Open a fast pipe to the corresponding adapter. See Chapter 8.2.3 "Operating Modes" on
2. Right-click on the
Adapter
node and select
Create Network...
:
– You can also click on the Create Network icon to do this.
3. The adapter DTM now scans the wired interface and automatically adds all the HART
devices found to the network (in this case, the temperature transmitter TMT162):
– Depending upon FieldCare configuration and number of devices, this may occur
automatically or after confirmation with
OK
in the Scanning Result dialog.
– Depending upon FieldCare configuration, if only one device is found, the
corresponding Device DTM will open, see below.
4. Repeat the process for all adapters in the network.
5. To open the Device DTM of an unconnected transmitter right-click on the Transmitter
node and select Connect, then right-click again and select Online Parameterization.