Waterpilot FMX21
Diagnostics and troubleshooting
Hauser
77
Failure current ≤ 3.6 mA or ≥ 21 mA
• Pt100 not connected correctly
Connect device as per → 25
• 4 to 20 mA cable not connected correctly
Connect device as per → 25
• Pt100 resistance thermometer defective
Replace the device
• Temperature head transmitter defective
Replace the temperature head transmitter
Measured value is inaccurate/incorrect
Pt100 connected in 2-wire circuit, cable resistance was not compensated for
Compensate for the cable resistance
Connect Pt100 as 3-wire or 4-wire circuit
10.5 Response of output to errors
The behavior of the current output in the event of errors is defined in the following
parameters:
• "Alarm behav. P (050)"
• "Output fail mode (190)"
• "High Alarm Curr. (052)"
10.6 Firmware history
Date
Firmware version
Modifications
Documentation
05.2009
01.00.zz
Original firmware.
Compatible with:
• FieldCare version 2.02.00 and higher
• Field Communicator DXR375 with Device Rev.: 1, DD Rev.: 1
BA00380P/00/EN/03.09
BA00380P/00/EN/07.09
BA00380P/00/EN/08.09
BA00380P/00/EN/13.11
BA00380P/00/EN/14.13
BA00380P/00/EN/15.15
BA00380P/00/EN/16.16
BA00380P/00/EN/17.16
BA00380P/00/EN/18.18