Description of device parameters
Waterpilot FMX21
102
Hauser
Description
Enter the number of the current point in the table. Subsequent entries in "X-val" and "Y-val"
relate to this point.
Input range
1...32
X-val
Write permission
Operators/Service engineers/Expert
Description
Enter the X-value (level before linearization) for the specific point in the table and confirm.
Note
• If "Lin. mode" = "Manual", the level value must be entered.
• If "Lin. mode" = "Semiautomatic", the level value is displayed and must be confirmed by
entering the paired Y-value.
Y-value
Write permission
Operators/Service engineers/Expert
Description
Enter the Y-value (value after linearization) for the specific point in the table. The unit is
determined by "Unit after lin.".
Note
The linearization table must be monotonic (increasing or decreasing).
Edit table
Write permission
Operators/Service engineers/Expert
Description
Select the function for entering the table.
Options
• Next point: Enter the next point.
• Current point: stay on the current point to correct a mistake for example.
• Last input point: skip back to previous point to correct a mistake for example.
• Insert point: Insert an additional point (see example below).
• Delete point: Delete the current point (see example below).
Example
Add point, in this case between the 4th and 5th point for example
• Select point 5 via the "Line-numb" parameter.
• Select the "Insert point" option via the "Edit table" parameter.
• Point 5 is displayed for the "Line-numb" parameter. Enter new values for the "X-val" and
"Y-val" parameters.
Delete point, in this case the 5th point for example
• Select point 5 via the "Line-numb" parameter.
• Select the "Delete point" option via the "Edit table" parameter.
• The 5th point is deleted. All of the following points are pushed up one number i.e.
following deletion, the 6th point becomes Point 5.
Содержание Waterpilot FMX21
Страница 143: ......
Страница 144: ...www addresses endress com 71593280 71593280...