Operating Instructions
RLN42
Two-channel NAMUR isolating amplifier with universal
power supply and relay signal output
BA02065K/09/EN/01.20
71526790
2020-12-17
Страница 1: ...Products Solutions Services Operating Instructions RLN42 Two channel NAMUR isolating amplifier with universal power supply and relay signal output BA02065K 09 EN 01 20 71526790 2020 12 17 ...
Страница 2: ...conditions 11 6 2 Quick wiring guide 12 6 3 Supply voltage 12 6 4 Post connection check 12 7 Operation options 13 7 1 Display and operating elements 13 8 Commissioning 14 8 1 Post installation check 14 8 2 Switching on the device 15 9 Diagnostics and troubleshooting 16 9 1 General troubleshooting 16 10 Maintenance 16 11 Repair 16 11 1 General information 16 11 2 Spare parts 16 11 3 Return 17 11 4 ...
Страница 3: ...ion Failure to avoid this situation can result in serious or fatal injury CAUTION This symbol alerts you to a dangerous situation Failure to avoid this situation can result in minor or medium injury NOTICE This symbol contains information on procedures and other facts which do not result in personal injury 1 2 2 Symbols for certain types of information Symbol Meaning Permitted Procedures processes...
Страница 4: ...nt and alternating current Ground connection A grounded terminal which as far as the operator is concerned is grounded via a grounding system 1 2 4 Symbols in graphics 1 2 3 Item numbers A B C Views 1 2 5 Symbols at the device Warning Observe the safety instructions contained in the associated Operating Instructions ...
Страница 5: ...ximity switches floating contacts and contacts with a resistive circuit A relay is available per channel as the signal output The device is designed for installation on DIN rails in accordance with IEC 60715 2 2 2 Product liability The manufacturer does not accept any responsibility for damage that results from non designated use and from failure to comply with the instructions in this manual 2 3 ...
Страница 6: ...d dry environment Do not expose the device to mechanical and or thermal stress that exceeds the specified limits The device is intended for installation in a cabinet or similar housing The device may only be operated as an installed device The cabinet must meet the fire protection housing requirements according to safety standard UL IEC 61010 1 and provide adequate protection against electric shoc...
Страница 7: ...tive coupling element is installed onsite directly at the contact to be monitored or in the sensor connection compartment 4 Incoming acceptance and product identification 4 1 Incoming acceptance Check the following during incoming acceptance Are the order codes on the delivery note and the product sticker identical Are the goods undamaged Do the nameplate data match the ordering information on the...
Страница 8: ...onsumption output 4 Approval in hazardous area with number of the relevant Ex documentation XA 5 Fieldbus communication logo 6 Firmware version and device revision 7 Approval logos 8 2 lines for the TAG name 4 2 2 Name and address of manufacturer Name of manufacturer Endress Hauser Wetzer GmbH Co KG Address of manufacturer Obere Wank 1 D 87484 Nesselwang Model type reference RLN42 4 3 Scope of del...
Страница 9: ...s The dimensions of the device are provided in the Technical data section of the Operating Instructions 5 1 2 Mounting location The device is designed for installation on 35 mm 1 38 in DIN rails in accordance with IEC 60715 TH35 The device s housing provides basic insulation from neighboring devices for 300 Veff If several devices are installed side by side this must be taken into consideration an...
Страница 10: ...king clip of the device click into place on the DIN rail 3 Pull gently on the device to check if it is correctly mounted on the DIN rail 5 3 Disassembling the DIN rail device 1 2 3 A0039696 3 Disassembling the DIN rail device 1 Insert a screwdriver into the tab of the DIN rail clip 2 Use the screwdriver to pull down on the DIN rail clip as shown in the diagram 3 Hold down the screwdriver to remove...
Страница 11: ...lectrostatic discharge Protect the terminals from electrostatic discharge 6 1 1 Special connection instructions Disconnecting units and auxiliary circuit protective systems with suitable AC or DC values must be provided in the building installation A switch power circuit breaker must be provided close to the device and clearly marked as a disconnecting unit for this device An overcurrent protectio...
Страница 12: ...t connection check Device condition and specifications Notes Are the device or cables free from damage visual check Do the ambient conditions match the device specification e g ambient temperature measuring range etc See Technical data Electrical connection Notes Does the supply voltage match the information on the nameplate U e g 24 to 230 VAC DC Are the power supply and signal cables connected c...
Страница 13: ...ine fault detection can be enabled or disabled via DIP switches DIP switch 1 channel 1 DIP switch 3 channel 2 All DIP switches are set to the I position when the device is delivered from the factory I normal phase operating current behavior II inverse phase closed circuit current behavior DIP switch 1 DIP switch position I normal function in the event of a 0 signal at the input the relay output ch...
Страница 14: ...tus 1 2 3 4 NO contact NC contact OUT yellow LF red Open Open Blocking OK I I I I Open Closed No Closed Closed Conducti ng OK I I I I Closed Open X No Open Open Blocking OK II I II I Closed Open X No Closed Closed Conducti ng OK II I II I Open Closed No Open Blocking OK I II I II Open Closed Yes Closed Conducti ng OK I II I II Closed Open X Yes Any state Any state Wire break I II I II Open Closed ...
Страница 15: ...ltage matches the voltage specifications on the nameplate Failure to perform these checks may result in damage to the device caused by the incorrect supply voltage 8 2 Switching on the device Switch on supply voltage The green LED display on the front of the device indicates that the device is operational ...
Страница 16: ...s defective Replace the device The status LED on the DIN rail device is lit or flashing red Diagnostics events as per NAMUR NE107 Check diagnostics events LED is lit diagnostic display category F LED flashing diagnostic display categories C S or M The power LED on the DIN rail device is not lit green Power failure or insufficient supply voltage Check the supply voltage and check if wiring is corre...
Страница 17: ...or a factory calibration are required or if the wrong device was ordered or delivered 11 4 Disposal If required by the Directive 2012 19 EU on waste electrical and electronic equipment WEEE the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste Do not dispose of products bearing this marking as unsorted municipal waste Instead return th...
Страница 18: ...with IEC 61508 A resistive coupling element 1 kΩ 10 kΩ is available as an optional accessory and can be used to monitor line faults of sensors with mechanical contacts The resistive coupling element is installed onsite directly at the contact to be monitored or in the sensor connection compartment Dependability We only provide a warranty if the device is installed and used as described in the Oper...
Страница 19: ...n data See associated XA Safety Instructions Galvanic isolation Input output Peak value as per EN 60079 11 375 V Input power supply Peak value as per EN 60079 11 375 V 12 4 Power supply Terminal assignment Quick wiring guide N L 24 230V AC DC Out In 5 1 4 2 4 1 3 3 2 2 3 1 2 1 3 2 2 3 5 3 1 2 1 1 14 14 11 11 12 12 Ch1 Ch1 Ch2 Ch2 A0043438 7 Terminal assignment RLN42 Supply voltage The modules are ...
Страница 20: ...t the input the output adopts the safe state in 40 ms 12 6 Installation Mounting location The device is designed for installation on 35 mm 1 38 in DIN rails in accordance with IEC 60715 TH35 The device s housing provides basic insulation from neighboring devices for 300 Veff If several devices are installed side by side this must be taken into consideration and additional insulation must be provid...
Страница 21: ...mportant ambient conditions Ambient temperature range 40 to 60 C 40 to 140 F Storage temperature 40 to 80 C 40 to 176 F Degree of protection IP 20 Overvoltage category III Pollution degree 2 Humidity 10 to 95 No condensation Altitude 2000 m 6562 ft Shock and vibration resistance Vibration resistance as per DNVGL CG 0339 2015 and DIN EN 60068 2 27 DIN rail device 2 to 100 Hz at 0 7g general vibrati...
Страница 22: ... on DIN rail 100 3 94 B H L A0044417 Width B x length L x height H with terminals 17 5 mm 0 69 in x 116 mm 4 57 in x 107 5 mm 4 23 in Weight Device with terminals values rounded up Approx 140 g 4 94 oz Color Light gray Materials All the materials used are RoHS compliant Housing polycarbonate PC flammability rating according to UL94 V 0 ...
Страница 23: ... switches DIP switch 1 channel 1 DIP switch 3 channel 2 All DIP switches are set to the I position when the device is delivered from the factory I normal phase operating current behavior II inverse phase closed circuit current behavior DIP switch 1 DIP switch position I normal function in the event of a 0 signal at the input the relay output changeover switches to the non conducting state NO conta...
Страница 24: ... I I I Closed Open X No Open Open Blocking OK II I II I Closed Open X No Closed Closed Conducti ng OK II I II I Open Closed No Open Blocking OK I II I II Open Closed Yes Closed Conducti ng OK I II I II Closed Open X Yes Any state Any state Wire break I II I II Open Closed X Yes Any state Any state Short circuit I II I II Open Closed X Yes Open Blocking OK II II II II Closed Open X Yes Closed Condu...
Страница 25: ...ific information such as measuring range or operating language Automatic verification of exclusion criteria Automatic creation of the order code and its breakdown in PDF or Excel output format Ability to order directly in the Endress Hauser Online Shop The Configurator is available on the Endress Hauser website at www endress com Click Corporate Select your country Click Products Select the produc...
Страница 26: ...the serial number from the nameplate or scan the 2D matrix code QR code on the nameplate Brief Operating Instructions KA Guide that takes you quickly to the 1st measured value The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning Operating Instructions BA Your reference guide These Operating Instructions contain all the information...
Страница 27: ...evices for these tasks are collectively known as isolating amplifiers or signal isolators and are available with different functions in the Endress Hauser RN Series Different types of signals are conditioned in this context 13 2 1 Types of signals Signals are referred to as analog signals if they can continuously assume every value between a minimum and maximum value e g 0 4 20 mA and are therefor...
Страница 28: ...so that sensor errors can also be detected by an analog evaluation unit This is sometimes referred to as the closed circuit current principle NAMUR sensors can adopt four states at the output Current of 0 mA wire break circuit open Current below 1 2 mA sensor ready undamped Current above 2 1 mA sensor ready damped Current of maximum value above 6 mA short circuit maximum current The portfolio of t...
Страница 29: ...s above or below the limit value for example The following are examples of typical applications of the RLN42 NAMUR isolating amplifier Each application is explained briefly and described in a schematic diagram Digital isolating amplification of NAMUR sensor signals from a hazardous area The passive Liquiphant FTL41 sensor with the FEL48 evaluation unit supplies a NAMUR signal value 1 2 mA or 2 1 m...
Страница 30: ...hazardous area Line monitoring for line breaks and short circuiting can be implemented with the resistance circuit in the resistive coupling element which is looped into the connection compartment of the FTE20 on the sensor side This monitoring function is described in greater detail in the NE21 Recommendations of the User Association of Automation Technology in Process Industries NAMUR Rs Rp A004...
Страница 31: ...nd operating elements Overview 13 23 Document Function 3 Document function 3 H Hardware settings Configuration 13 23 L Line fault detection 13 23 N Nameplate 7 O Operation options Local operation 13 23 Operational safety 5 P Product safety 6 R Requirements for personnel 5 Return 17 S Safety Instructions XA 26 T Terminal assignment 12 19 Troubleshooting General errors 16 W Workplace safety 5 ...
Страница 32: ...www addresses endress com 71526790 71526790 ...