RID16
Operation via FOUNDATION™ Fieldbus
Hauser
49
11.3
Transducer Blocks
The Transducer Blocks of the RID1x contain all the device-specific parameters. All the settings
directly connected with the display are made here.
11.3.1
Selecting the operating mode
The operating mode is set by means of the MODE_BLK parameter group (page 51). The Transducer
Block supports the following operating modes:
• AUTO (automatic mode)
• OOS (out of service)
!
Note!
The OOS block status is also displayed by means of the BLOCK_ERR parameter (page 51).
11.3.2
Accessing the manufacturer-specific parameters
To access the manufacturer-specific parameters, the hardware write protection must be deactivated
(see Section 5.5).
39
Write Priority
(WRITE_PRI)
AUTO - OOS
Specifies the behavior of a write protected alarm ("WRITE_ALM" parameter).
User input:
0 =
1 =
2 =
3-7 =
8-15 =
The write protection alarm is not evaluated.
No report to the fieldbus host system in the event of a
write protection alarm.
Reserved for block alarms.
The write protection alarm is output with the
appropriate priority (3 = low priority, 7 = high priority)
to the fieldbus host system as a user notice.
The write protection alarm is output with the
appropriate priority (8 = low priority, 15 = high
priority) to the fieldbus host system as a critical alarm.
Factory default:
0
Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description