RIA15
Wiring
Hauser
17
T10
A0018908
å
7
Ground terminal on field housing
5.5
Degree of protection
5.5.1
Field housing
The devices meet all the requirements of IP66. It is absolutely essential to comply with the
following points to ensure this protection is guaranteed after mounting or servicing the device:
• The housing seal must be clean and undamaged when inserted into the groove. The seal
must be cleaned, dried or replaced if necessary.
• The cables used for connection must be of the specified outside diameter (e.g. M16 x 1.5,
cable diameter 5 to 10 mm (0.2 to 0.39 in)).
• Mount the measuring device in such a way that the cable entries point downwards.
• Replace unused cable entries with dummy plugs.
• The grommet used should not be removed from the cable entry.
• The housing covers and the cable entries must be firmly tightened.
5.5.2
Panel housing
The front of the device meets the requirements of IP65. It is absolutely essential to comply
with the following points to ensure this protection is guaranteed after mounting or servicing
the device:
• The seal between the front of the housing and the panel must be clean and undamaged.
The seal must be cleaned, dried or replaced if necessary.
• The threaded rods of the panel mounting clips must be firmly tightened.
5.6
Post-connection check
Device condition and specifications
Notes
Are cables or the device damaged?
Visual inspection
Electrical connection
Notes
Does the supply current match the specifications on the nameplate?
-