Commissioning
Prosonic S FMU95
68
E Hauser
6.3
Parametrization of the Analog Input Blocks
The measured values are transmitted to the PLC via the Analog Input Blocks of the Prosonic S. The
Prosonic S FMU95 provides 20 Analog Input Blcks. They are parametrized in the parameter set
"output calculations/analog input/analog input N" (N = 1 to 20). The parameters of this set are
described in this section.
6.3.1
"analog input N" (N = 1 - 20)
"measured value N" (N = 1 - 20)
Use this parameter to select the measured or calulated variable which is transferred by the AI block.
Selection
• none
• level N (N = 1 to10)
• sum N (N = 1 to 5)
• average N (N = 1 to 5)
• temperature sensor N (N = 1 to 10)
• distance sensor N (N = 1 to10)
!
Note!
If
"sum N"
or
"average N"
are selected, the Prosonic S returns to the "analog input N" parameter
set, which now contains the parameters
"level 1"
to
"level 10"
. Select
"yes"
for each parameter
which is to be included in the sum or average. Select
"no"
(default) if the respective parameter is
not to be included in the sum or average.
Default setting for 5 sensor inputs
• measured value 1 = level 1
• ...
• measured value 5 = level 5
• measured value 6 = none
• ...
• measured value 20 = none
Default setting for 10 sensor inputs
• measured value 1 = level 1
• ...
• measured value 10 = level 10
• measured value 11 = none
• ...
• measured value 20 = none
"value"
Displays the current value of the measured or calculated variable.
"status"
Displays the status which is transferred with the measured value.
analog input 1
01A02
measured value 1:
value:
status: