Prosonic M FMU42 HART
Diagnostics and troubleshooting
Hauser
35
A512 = Recording of mapping
Alarm ends after a few seconds
A521 = New sensor type identified
Perform a reset
A671 = Linearization not complete, not usable
Perform the basic setup
E281 = Wire breakage at temperature sensor
Replace the sensor and/or electronics
E641 = No usable echo
Check the basic setup
E651 = Level in safety distance, risk of overspill
• The error disappears as soon as the level is no longer in the safety distance
• Acknowledge alarm
Safety settings (01)
function group →
Acknowledge alarm (017)
function
E661 = Sensor temperature too high
W103 = Initializing
If the message does not disappear, replace the electronics
W153 = Initializing
• Wait a few seconds
• If the error remains active, switch the voltage off/on
W601 = Linearization curve not monotone
Correct the table, enter a table that increases monotonically
W611 = Less than 2 linearization points
Enter more value pairs
W621 = Simulation on
Switch off the simulation mode,
Output (06)
function group →
Simulation (065)
function
W681 = Current out of range
• Perform the basic setup
• Check linearization
W691 = Noise filling
10.5 Application errors
Error:
Measured value (000)
incorrect, measured
distance (008)
correct.
Example:
100%
F
0%
t →
A
B
D (008)
E
A0038459
A
Expected result
B
Error occurred
1. Check
Empty calibration (005)
and
Full calibration (006)
and correct.
Содержание Prosonic M FMU42