Prosonic Flow 92
11 Description of device functions
Hauser
87
Further information on
the “CURRENT SPAN
(OUTPUT)” function
How the current output responds under the following
conditions:
1.
Defined measuring range (
➀
-
➁
):
and the following flow behaviour:
• STANDARD
The current output signal is proportional to the measured variable. The
flow components outside the scaled measuring range are not taken into
account for signal output.
• SYMMETRY
The current output signal is independent of the direction of flow.
Failsafe Mode (Output)
For safety reasons it is advisable to ensure that the current output assumes a
predefined state in the event of a fault.
Options:
HOLD VALUE – MIN. CURRENT – MAX. CURRENT – ZERO
HOLD VALUE
Measured value output is based on the last measured value saved before
the error occurred.
MIN. CURRENT
Output current = 0.8 mA (–20 %; independent of the setting selected in the
function “CURRENT SPAN”, see Page 86)
MAX. CURRENT
Output current = 23.2 mA (+20 %; independent of the setting selected in the
function “CURRENT SPAN”, see Page 86)
ZERO
Output current = 4.0 mA (0.0 %; independent of the setting selected in the
function “CURRENT SPAN”, see Page 86)
Factory setting:
HOLD VALUE
Inputs and Outputs
F-xxxxxxx-05-xx-xx-xx-003
Q
20
4
0
➀
➁
mA
F-x3xxxxx-05-xx-xx-xx-008
t
mA
F-x3xxxxx-05-xx-xx-xx-009
F-x3xxxxx-05-xx-xx-xx-010
t
mA
Содержание prosonic flow 92
Страница 4: ...Brief operating instructions Prosonic Flow 92 4 Endress Hauser...
Страница 12: ...2 Identification Prosonic Flow 92 12 Endress Hauser...
Страница 26: ...3 Installation Prosonic Flow 92 26 Endress Hauser...
Страница 34: ...4 Wiring Prosonic Flow 92 34 Endress Hauser...
Страница 40: ...5 Operation Prosonic Flow 92 40 Endress Hauser...
Страница 46: ...7 Maintenance Prosonic Flow 92 46 Endress Hauser...
Страница 96: ...Index Prosonic Flow 92 96 Endress Hauser...