Prosonic Flow 92
10 Technical data
Hauser
55
10
Technical data
10.1
Brief technical data guide
10.1.1
Application
• Measuring the flow rate of fluids in closed piping systems.
• Applications in measuring, control and regulation technology for temporary process
surveying.
10.1.2
Function and system design
Measuring principle
Prosonic Flow 92 operates on the principle of transit time difference.
Measuring system
The flow measuring system consists of a transmitter and sensors.
Transmitter:
• Prosonic Flow 92
Flow measuring sensors:
• Prosonic Flow W
for nominal diameters DN 50...4000
• Prosonic Flow U
for nominal diameters DN 15...100
• Prosonic Flow P
for nominal diameters DN 50...300
10.1.3
Input
Measured variable
Flow velocity (transit time difference proportional to flow velocity)
Measuring range
Prosonic Flow W, P, U sensors typically v = 0...7 m/s with the specified measuring accu-
racy
Operable flow range
Over 70 : 1
Input signal
Current input: 4...20 mA, galvanically not isolated
10.1.4
Output
Output signal
Current output:
Active 4...20 mA, R
L
= 0...1 kW, galvanically isolated (from ground and analog input)
Signal on alarm
Current output
→
failsafe mode selectable
Load
See “Output signal”
Low flow cut-off
Switch point for low flow cut-off is selectable.
Galvanic isolation
All circuits for outputs and power supply are galvanically isolated from each other.
Содержание prosonic flow 92
Страница 4: ...Brief operating instructions Prosonic Flow 92 4 Endress Hauser...
Страница 12: ...2 Identification Prosonic Flow 92 12 Endress Hauser...
Страница 26: ...3 Installation Prosonic Flow 92 26 Endress Hauser...
Страница 34: ...4 Wiring Prosonic Flow 92 34 Endress Hauser...
Страница 40: ...5 Operation Prosonic Flow 92 40 Endress Hauser...
Страница 46: ...7 Maintenance Prosonic Flow 92 46 Endress Hauser...
Страница 96: ...Index Prosonic Flow 92 96 Endress Hauser...