Proline Prosonic Flow 90
3 Installation
Hauser
29
3.3.8
Installing the measuring sensors Prosonic Flow W
(single path Insertion version)
1.
Determine the installation area (e) on the pipe section:
– Installation location: Page 14
– Inlet/outlet runs: Page 16
– Space required by the measuring point approx. 1x pipe diameter.
2.
Mark the middle line on the pipe at the mounting location and mark the position of the first
drillhole (drillhole diameter: 65 mm).
!
Note!
Make the middle line longer than the drillhole!
A0001124
Fig. 24:
Installing the measuring sensors, steps 1 and 2
3.
Drill the first hole, e.g. with a plasma cutter. If the wall thickness of the pipe is unknown,
measure it at this point.
4.
Determine the sensor distance.
!
Note!
To determine the sensor distance use:
– the “Sensor Installation” Quick Setup menu if the measuring device has a local operation.
Use the Quick Setup as described on Page 64. The sensor distance is shown in the SENSOR
DISTANCE function. The transmitter has to be installed and connected to the power supply
to carry out the “Sensor Installation” Quick Setup.
– the procedure described on Page 67 ff. if the measuring device has no local operation.
A0001125
Fig. 25:
Installing the measuring sensors, steps 3 and 4
e
Содержание Prosonic Flow 90
Страница 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Страница 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Страница 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Страница 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Страница 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Страница 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Страница 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Страница 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Страница 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...