Proline t-mass 65 PROFIBUS DP/PA
Wiring
Hauser
35
4.5
Post-connection check
Perform the following checks after completing electrical installation of the measuring device:
Device condition and specifications
Notes
Are cables or the device damaged (visual inspection)?
-
Electrical connection
Notes
Does the supply voltage match the specifications on the nameplate?
85 to 260 V AC (45 to 65 Hz)
20 to 55 V AC (45 to 65 Hz)
16 to 62 V DC
Do the cables comply with the specifications?
Sensor cable
Do the cables have adequate strain relief?
-
Cables correctly segregated by type?
Without loops and crossovers?
-
Are the power supply and signal cables correctly connected?
See the wiring diagram inside the cover
of the terminal compartment
Only remote version: Is the flow sensor connected to the matching transmitter
electronics?
Check serial number on nameplates of
sensor and connected transmitter.
Only remote version: is the connecting cable between sensor and transmitter
connected correctly?
Are all screw terminals firmly tightened?
-
Are all cable entries installed, firmly tightened and correctly sealed?
Cables looped as "water traps"?
Are all housing covers installed and firmly tightened?
-
Electrical connection, PROFIBUS
Notes
Are all the connecting components (T-boxes, junction boxes, connectors, etc.)
connected with each other correctly?
-
Has each fieldbus segment been terminated at both ends with a bus
terminator?
Has the max. length of the fieldbus cable been observed in accordance with
the PROFIBUS specifications?
Has the max. length of the spurs been observed in accordance with the
PROFIBUS specifications?
Is the fieldbus cable fully shielded and correctly grounded?