Proline t-mass 65 PROFIBUS DP/PA
Commissioning
Hauser
77
Assignment of the measured variables to the TOTAL module
The TOTAL module can transmit different totalizer variables to the PROFIBUS Master (class
1).
The measured variables are assigned to the totalizer function blocks 1 to 2 by means of the
local display or with the aid of an operating program (e.g. FieldCare) in the CHANNEL func-
tion:
• TOTALIZER
SELECT TOTALIZER: Selection of a totalizer
• COMMUNICATION
CHANNEL: Selection of a measured variable
Possible settings
Factory setting
SETTOT_TOTAL module
The module combination SETTOT_TOTAL (slots 4 to 5) consists of the functions SETTOT
and TOTAL. With this module combination:
• The totalizer can be controlled via the PROFIBUS Master (SETTOT).
• The totalizer value, is transmitted, including the status (TOTAL).
SETTOT function
In the SETTOT function, the totalizer can be controlled via control variables.
The following control variables are supported:
• 0 = Totalize (factory setting)
• 1 = Reset totalizer (the totalizer value is reset to 0)
• 2 = Accept totalizer preset
!
Note!
After the totalizer value has been reset to 0 or set to the preset value, the totalizing contin-
ues automatically. The control variable does not have to be changed to 0 again to restart
totalizing.
Stopping totalizing is controlled in the SETTOT_MODETOT_TOTAL module via the
MODETOT function.
TOTAL function
For a description of the TOTAL function, refer to TOTAL module
Data structure of the SETTOT_TOTAL module combination
Totalizer value/measured variable
ID for CHANNEL function
MASS FLOW
277
CORR. VOLUME FLOW
398
OFF
0
Module
Totalizer
function block
Totalizer value/
Measured variable
ID for CHANNEL function
TOTAL (slot 4)
1
MASS FLOW
277
TOTAL (slot 5)
2
MASS FLOW
277
Output data
Input data
SETTOT
TOTAL
Byte 1
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Control
Totalizer value (IEEE 754 floating point number)
Status
Содержание Proline t-mass 65 PROFIBUS DA