Technical data
Proline t-mass 65 PROFIBUS DP/PA
112
Hauser
• When mounting, please note that the recommended upstream distances should be
doubled for very light gases such as helium and hydrogen.
Input signal
Status input (auxiliary input)
U = 3 to 30 V DC, R
i
= 3 k
, galvanically isolated. Switch level: ±3 to ±30 V DC, independent
of polarity
Configurable for: positive zero return, reset error messages
11.4
Output
Output signal
PROFIBUS DP interface:
• PROFIBUS DP in accordance with EN 50170 Volume 2
• Profile Version 3.0
• Data transmission rate: 9.6 kBaud to 12 MBaud
• Automatic data transmission rate recognition
• Signal encoding: NRZ Code
• Function blocks: 3 × Analog Input, 2 × Totalizer
• Output data: Mass flow, Heat flow, Corrected volume flow, Temperature, Totalizer 1 to 2
• Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode,
Totalizer control
• Bus address can be configured via miniature switches or via the local display (optional)
• Available output combination
PROFIBUS PA interface:
• PROFIBUS PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP),
galvanically isolated
• Data transmission rate: 31.25 kBaud
• Current consumption: 11 mA
• Permitted supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Signal coding: Manchester II
• Function blocks: 3 × Analog Input, 2 × Totalizer
• Output data: Mass flow, Heat flow, Corrected volume flow, Temperature, Totalizer 1 to 2
• Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode,
Totalizer control
• Bus address can be configured via miniature switches or via the local display (optional)
• Available output combination
Signal on alarm
Status and alarm messages in accordance with PROFIBUS Profile Version 3.0
Low flow cut off
Switch points for low flow cut off are programmable.
Factory setting = 1% of 20 mA Value
Galvanic isolation
All circuits for inputs, outputs and power supply are galvanically isolated from each other.