Installation
Proline Prosonic Flow 93 PROFIBUS DP/PA
46
Hauser
3.11.1
Installation for measurement as single-path insertion version
1.
Determine the installation area (e) on the pipe section:
– Mounting location
– Inlet/outlet run
– Space required by the measuring point: approx. 1× pipe diameter.
2.
Mark the middle line on the pipe at the mounting location and mark the position of the first
drillhole (drillhole diameter: 65 mm / 2.56").
!
Note!
Make the middle line longer than the drillhole!
A0001124
Fig. 47:
Installing the measuring sensors, steps 1 and 2
3.
Cut the first hole, e.g. with a plasma cutter. Measure the wall thickness of the pipe if it is not
known.
4.
Determine the sensor distance.
!
Note!
Determine the sensor distance as follows:
– Via the Quick Setup "Sensor Installation" for measuring devices with local operation.
Run the Quick Setup as described on
90. The sensor distance is displayed in the
SENSORABSTAND function. The transmitter must be installed and connected to the power
supply before you can run the "Sensor Installation" Quick Setup.
– As explained on
90 for transmitters without local operation.
A0001125
Fig. 48:
Installing the measuring sensors, steps 3 and 4
5.
Draw the sensor distance (a) starting from the middle line of the first drillhole.
e