Proline Prosonic Flow 93 PROFIBUS DP/PA
Troubleshooting
Hauser
137
9.2
System error messages
Serious system errors are
always
recognized by the instrument as "Fault message" and are shown
as a lightning flash (
$
) on the display! Fault messages immediately affect the outputs. Simulations
and positive zero return, on the other hand, are classed and displayed as "Notice messages".
"
Caution!
In the event of a serious fault, a flowmeter might have to be returned to the manufacturer for repair.
Important procedures must be carried out before you return a flowmeter to Hauser
Always enclose a duly completed "Declaration of Contamination" form. A copy of the form can be
found at the end of these Operating Instructions!
!
Note!
See the information on
9.2.1
Displaying the device status on PROFIBUS DP/PA
Display in the operating program (acyclic data transmission)
The device status can be queried using an operating program (e.g. FieldCare):
Function block SUPERVISION
→
SYSTEM
→
OPERATION
→
ACTUAL SYSTEM CONDITION
Display in the PROFIBUS master system (cyclic data transmission)
If the AI or TOTAL modules are configured for cyclic data transmission, the device status is coded
in accordance with PROFIBUS Profile Specification 3.0 and transmitted with the measured value to
the PROFIBUS master (Class 1) by means of the quality byte (byte 5). The quality byte is split into
the "quality status", "quality substatus" and "limits" segments.
a0002707-en
Fig. 96:
Structure of the quality byte
The content of the quality byte depends on the failsafe mode error behavior configured in the
corresponding Analog Input function block. Depending on which failsafe mode has been set in the
FAILSAFE_TYPE function, the following status information is transmitted to the PROFIBUS master
(Class 1) via the quality byte:
• For FAILSAFE_TYPE
→
FSAFE VALUE:
Quality
Code
Measuring value
Limits
Quality Substatus
Quality
Status
Byte 5
Quality code (HEX)
Quality status
Quality substatus
Limits
0x48
0x49
0x4A
UNCERTAIN
Substitute set
OK
Low
High
Содержание Proline Prosonic Flow 93