Technical data
Proline Promass E 300 Modbus RS485
178
Hauser
Supported baud rate
• 1
200 BAUD
• 2
400 BAUD
• 4
800 BAUD
• 9
600 BAUD
• 19
200 BAUD
• 38
400 BAUD
• 57
600 BAUD
• 115
200 BAUD
Data transfer mode
• ASCII
• RTU
Data access
Each device parameter can be accessed via Modbus RS485.
For Modbus register information
Compatibility with
earlier model
If the device is replaced, the measuring device Promass 300 supports the
compatibility of the Modbus registers for the process variables and the
diagnostic information with the previous model Promass 83. It is not
necessary to change the engineering parameters in the automation system.
System integration
Information on system integration → 70.
• Modbus RS485 information
• Function codes
• Register information
• Response time
• Modbus data map
16.5 Power supply
Terminal assignment
Supply voltage
Order code for
"Power supply"
Terminal voltage
Frequency range
Option
D
DC 24 V
±20%
–
Option
E
AC 100 to 240 V –15 to +10%
50/60 Hz
Option
I
DC 24 V
±20%
–
AC 100 to 240 V –15 to +10%
50/60 Hz
Power consumption
Transmitter
Max. 10 W (active power)
switch-on current
Max. 36 A (<5 ms) as per NAMUR Recommendation NE 21
Current consumption
Transmitter
• Max. 400 mA (24 V)
• Max. 200 mA (110 V, 50/60 Hz; 230 V, 50/60 Hz)
Power supply failure
• Totalizers stop at the last value measured.
• Depending on the device version, the configuration is retained in the device memoryor in
the pluggable data memory (HistoROM DAT).
• Error messages (incl. total operated hours) are stored.
Electrical connection