4 Wiring
Proline Promass 83 FOUNDATION Fieldbus
30
Hauser
F06-xxxFFxxx-04-03-xx-xx-000
Fig. 19:
Connecting the transmitter (wall-mount housing). Cable cross section: max. 2.5 mm
2
a
Cable for power supply: 85...260 V AC, 20...55 V AC, 16...62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L
−
for DC
b
Fieldbus cable:
Terminal No. 26: FF+ (with integrated reverse polarity protection)
Terminal No. 27: FF– (with integrated reverse polarity protection)
c
Ground terminal for protective conductor
d
Ground terminal for fieldbus cable shielding (for notes on connection
e
Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF-Tool/Fieldtool package)
f
Cover of the connection compartment
4.3.2
Terminal assignment
Electrical values for inputs and outputs
Terminal No. (inputs/outputs)
Order variant
20 (+) / 21 (–)
22 (+) / 23 (–)
24 (+) / 25 (–)
26 (+) / 27 (–)
Fixed communication boards (permanent assignment)
83***-***********G
-
-
-
FOUNDATION
Fieldbus Ex i
83***-***********K
-
-
-
FOUNDATION
Fieldbus
1
2
c
d
e
a
a
b
b
22 23
20 21
24 25 26 27
f
FF+ FF–
L1 (L+)
N (L-)
Содержание Proline Promass 83
Страница 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Страница 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Страница 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Страница 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Страница 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Страница 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...