Proline Promag P 200
Hauser
11
HART load
• Min. 250 Ω
• Max.500
W
Dynamic variables
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
Power supply
Terminal assignment
Transmitter
4-20 mA HART connection version with additional outputs
–
4
+
1
–
2
+
3
1
2
3
A0013570
+
1
–
2
–
4
+
3
1
2
3
A0018161
Maximum number of terminals, without integrated overvoltage
protection
Maximum number of terminals, with integrated
overvoltage protection
1
2
3
Output 1 (passive): supply voltage and signal transmission
Output 2 (passive): supply voltage and signal transmission
Ground terminal for cable shield
Order code for
"Output"
Terminal numbers
Output 1
Output 2
1 (+)
2 (-)
3 (+)
4 (-)
Option
A
4-20 mA HART (passive)
-
Option
B
1)
4-20 mA HART (passive)
Pulse/frequency/switch output
(passive)
1)
Output 1 must always be used; output 2 is optional.
Supply voltage
An external power supply is required for each output. The following supply voltage values apply for the 4-20
mA HART current output:
Order code for
"Output"
Minimum terminal voltage
1)
2)
Maximum terminal voltage
• Option
A
: 4-20 mA HART
• Option
B
: 4-20 mA HART, pulse/
frequency/switch output
For 4 mA:
³
DC18 V
For 20 mA:
³
DC14 V
DC 35 V