Device functions Proline Promag 55 FOUNDATION Fieldbus
3 Transducer Block
Hauser
77
The CHANNEL parameter in the Analog Input function block is used to assign which process
variable is read in and processed in the downstream Analog Input function block:
• Process variable Calculated Mass Flow
→
CHANNEL 1 (Analog Input function block)
• Process variable Volume Flow
→
CHANNEL 2 (Analog Input function block)
• Process variable Totalizer 1
→
CHANNEL 7 (Analog Input function block)
• Process variable Totalizer 2
→
CHANNEL 8 (Analog Input function block)
• Process variable Totalizer 3
→
CHANNEL 9 (Analog Input function block)
3.2.2
Selecting the operating mode
The operation mode is set by means of the MODE_BLK parameter group. The Transducer Blocks
support the following operation modes:
• AUTO (automatic mode)
• OOS (out of service)
!
Note!
• The block status OOS is also shown via the parameter BLOCK_ERR. In operating mode OOS, if
write protection is not enabled and the access code is entered, you can access all the write
parameters without restriction.
• The following applies for the "Flow" and "Totalizer" Transducer Blocks: With the "OOS" operating
mode, the process variables are updated but the status of the output value OUT (AI Block) changes
to "BAD".
• If problems occur during the configuration of the function blocks
→
see Operating Instructions
for Proline Promag 55 FOUNDATION Fieldbus (BA126D), "Troubleshooting" section.
3.2.3
Alarm detection and processing
The Transducer Blocks do not generate any process alarms. The status of the process variables is
evaluated in the downstream Analog Input function blocks. If the Analog Input function block does
not receive an input value that can be evaluated from the "Flow" or "Totalizer" Transducer Blocks,
then a process alarm is generated. This process alarm is displayed in the BLOCK_ERR parameter of
the Analog Input function block (BLOCK_ERR = Input Failure).
The parameter BLOCK_ERR of the Transducer Blocks displays the device error that produced the
input value that could not be evaluated and thus triggered the process alarm in the Analog Input
function block.
In addition, the active device error is displayed via the "Diagnosis" Transducer Block in the
"Diagnosis - Act.Sys. Condition" parameter (
Page 90).
For further information on rectifying errors
→
see
Operating Instructions for Proline Promag 55
FOUNDATION Fieldbus (BA126D), "Troubleshooting" section.
3.2.4
Diagnosis
The status of the device is displayed via the following parameters specified in the FOUNDATION
Fieldbus specification:
• BLOCK_ERR
• Transducer Error
More detailed information on the current device status is displayed via the "Diagnosis" Transducer
Block in the manufacturer-specific parameter "Diag. - Act.Sys.Condition" (
For further information on rectifying errors
→
see Operating Instructions for Proline Promag 55
FOUNDATION Fieldbus (BA126D), "Troubleshooting" section.
Содержание Proline Promag 55
Страница 60: ...8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus 60 Endress Hauser ...
Страница 66: ...10 Index local operation Device Functions Proline Promag 55 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 68: ...Table of contens FOUNDATION Fieldbus Device Functions Proline Promag 55 FOUNDATION Fieldbus 68 Endress Hauser ...
Страница 129: ...Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress Hauser 129 ...
Страница 130: ...www endress com worldwide BA127D 06 en 09 06 71032705 FM SGML 6 0 ...