Device Functions Proline Promag 55 FOUNDATION Fieldbus
7 Block BASIC FUNCTION
Hauser
41
7.1
Group FOUNDATION FIELDBUS
7.1.1
Function group CONFIGURATION
BASIC FUNCTION
G
⇒
FOUNDATION FIELDBUS GGA
⇒
CONFIGURATION
620
Function description
BASIC FUNCTION
→
FOUNDATION FIELDBUS
→
CONFIGURATION
WRITE PROTECT
(6200)
Use this function to check whether the measuring device can be write-accessed via the
fieldbus.
User interface:
OFF
→
Write access via FOUNDATION Fieldbus possible
ON
→
Write access via FOUNDATION Fieldbus not possible
Factory setting:
OFF
!
Note!
Hardware write protection is activated and deactivated by means of a jumper on the I/O
board (
→
see Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
SIMULATION
(6201)
Use this function to check whether a simulation in the Analog Input or Discrete Output
function block is possible.
User interface:
OFF
→
Simulation in the Analog Input and Discrete Output function block is
not
possible.
ON
→
Simulation in the Analog Input and Discrete Output function block is possible
Factory setting:
ON
!
Note!
• The simulation mode is enabled and disabled by means of a jumper on the I/O board
(
→
see also Operating Instructions for Proline Promag 55 FOUNDATION Fieldbus).
• The status of the simulation mode is also shown in the parameter BLOCK_ERR of the
Resource Block.
DEVICE PD-TAG
(6203)
Use this function to enter a tag name for the measuring device.
User input:
Max. 32-character text, permissible: A-Z, 0-9, +,–, punctuation marks
Factory setting:
E+H_PROMAG_55_XXXXXXXXXXX
Содержание Proline Promag 55
Страница 60: ...8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus 60 Endress Hauser ...
Страница 66: ...10 Index local operation Device Functions Proline Promag 55 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 68: ...Table of contens FOUNDATION Fieldbus Device Functions Proline Promag 55 FOUNDATION Fieldbus 68 Endress Hauser ...
Страница 129: ...Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress Hauser 129 ...
Страница 130: ...www endress com worldwide BA127D 06 en 09 06 71032705 FM SGML 6 0 ...