Troubleshooting
Proline Promag 55 FOUNDATION Fieldbus
86
Hauser
9.2.1
List of system error messages
No.
Error messages:
FOUNDATION Fieldbus
(FF)*
(local display)
Transducer Block
error messages
Analog Input function block
error messages
Cause/remedy
* With FF, error messages are displayed in the "Diagnosis" Transducer Block (base index: 1600) by means of the "Diag. – Act.Sys.Condition" parameter
(manufacturer-specific).
S = System error
$
= Fault message (with an effect on operation)
! = Notice message (without an effect on operation)
No. # 0xx
→
Hardware error
001
Device status message (FF):
ROM/RAM failure –
Err. No. 001
Local display:
S: CRITICAL FAIL.
$
: # 001
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
ROM/RAM error. Error when accessing the
program memory (ROM) or random access
memory (RAM) of the processor.
Remedy:
Replace the amplifier board.
Spare parts
Transducer_Error = Electronics
failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
011
Device status message (FF):
Amplifier EEPROM failure –
Err. No. 011
Local display:
S: AMP HW EEPROM
$
: # 011
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Amplifier with faulty EEPROM
Remedy:
Replace the amplifier board.
Spare parts
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
012
Device status message (FF):
Amplifier EEPROM data
inconsistent –
Err. No. 012
Local display:
S: AMP SW EEPROM
$
: # 012
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
Error when accessing data of EEPROM measuring
amplifier
Remedy:
Perform a "warm restart" (i.e. restart the measuring
system without disconnecting mains power).
• FF: "Diagnosis" Transducer Block (base index:
1600)
→
"Sys. – Reset" RESTART SYSTEM
parameter
• Local display: SUPERVISION
→
SYSTEM
→
OPERATION
→
SYSTEM RESET
(
→
RESTART SYSTEM)
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
031
Device status message (FF):
S-DAT failure / S-DAT not
inserted –
Err. No. 031
Local display:
S: SENSOR HW DAT
$
: # 031
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Cause:
1.
S DAT is not correctly plugged into the
amplifier board (or is missing).
2.
S-DAT is defective.
Remedy:
1.
Check whether the S-DAT is correctly plugged
into the amplifier board,
2.
Replace the S-DAT if it is defective.
Spare parts
Check whether the new replacement DAT is
compatible with the existing electronics.
Check the:
- Spare part set number
- Hardware revision code
3.
Replace measuring electronics boards if
necessary Spare parts
4.
Plug the S-DAT into the amplifier board.
Transducer_Error = Electronics
failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)
032
Device status message (FF):
S-DAT data inconsistent –
Err. No. 032
Local display:
S: SENSOR SW DAT
$
: # 032
BLOCK_ERR = Device needs
maintenance now
OUT. QUALITY = BAD
Transducer_Error = Data
integrity error
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Input Failure
(faulty input value from
Transducer Blocks)