Technical data
Proline Promag 55 FOUNDATION Fieldbus
100
Hauser
10.1.4
Output
Output signal
Physical data transmission (Physical Layer Type):
• Fieldbus interface in accordance with IEC 61158-2
• Corresponds to device version type 112 of the FOUNDATION Fieldbus specification: type 112
standard data transfer (±9 mA, symmetrical), separate supply to field device (4-wire), intrinsically
safe version of the FF interface
• With integrated reverse polarity protection
Signal on alarm
Status messages as per FOUNDATION Fieldbus specification
Link Master (LM)
support
Yes
Link Master
(factory setting)/Basic Device
can be selected
Yes
Device basic current
12 mA
Device starting current
< 12 mA
Device error current (FDE)
0 mA
Device (lift off)
min. voltage
9 V (H1 segment)
Permissible fieldbus supply
voltage
9 to 32 V
Integrated reverse polarity
protection
Yes
ITK Version
5.01
Number of VCRs (total)
38
Number of link objects in VFD
40
Galvanic isolation
All circuits for inputs, outputs and power supply are galvanically isolated from each other.
Data transmission rate
31.25 kbit/s, voltage mode
Bus times
Min. idle time between two telegrams:
MIN_INTER_PDU_DELAY = 6 octet time (transfer time per octet)