8 Block SUPERVISION
Device Functions Proline Promag 55 FOUNDATION Fieldbus
54
Hauser
8.1
Group SYSTEM
8.1.1
Function group CONFIGURATION
SUPERVISION
J
⇒
SYSTEM
JAA
⇒
CONFIGURATION
800
Function description
SUPERVISION
→
SYSTEM
→
CONFIGURATION
ALARM DELAY
(8005)
Use this function to define a time span in which the criteria for a fault have to be satisfied
without interruption before a fault or notice message is generated.
Depending on the setting and the type of fault, this suppression acts on:
• Display
• Output blocks (AI Blocks) FOUNDATION Fieldbus interface
User input:
0 to 100 s (in steps of one second)
Factory setting:
0 s
"
Caution!
If this function is activated, fault and notice messages are delayed by the time
corresponding to the setting before being transmitted to the higher-order controller
(process controller, etc.). It is therefore imperative to check in advance in order to make
sure whether a delay of this nature could affect the safety requirements of the process. If
fault and notice messages may not be suppressed, a value of 0 seconds must be entered
here.
PERMANENT STORAGE
(8007)
This function displays whether permanent saving of all parameters in the EEPROM is
switched on or off.
User interface:
OFF
ON
Factory setting:
ON
Содержание Proline Promag 55
Страница 60: ...8 Block SUPERVISION Device Functions Proline Promag 55 FOUNDATION Fieldbus 60 Endress Hauser ...
Страница 66: ...10 Index local operation Device Functions Proline Promag 55 FOUNDATION Fieldbus 66 Endress Hauser ...
Страница 68: ...Table of contens FOUNDATION Fieldbus Device Functions Proline Promag 55 FOUNDATION Fieldbus 68 Endress Hauser ...
Страница 129: ...Device Functions Proline Promag 55 FOUNDATION Fieldbus Endress Hauser 129 ...
Страница 130: ...www endress com worldwide BA127D 06 en 09 06 71032705 FM SGML 6 0 ...