Promag 50
Installation
Hauser
17
3.2.5
Foundations, supports
If the nominal diameter is DN
350, mount the sensor on a foundation of adequate load-bearing
strength.
"
Caution!
Risk of damage.
Do not support the weight of the sensor on the metal casing: the casing would buckle and damage
the internal magnetic coils.
A0003209
Fig. 14:
Correct support for large nominal diameters (DN
350)
3.2.6
Adapters
Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-
diameter pipes.
The resultant increase in the rate of flow improves measuring accuracy with very slow-moving
fluids. The nomogram shown here can be used to calculate the pressure loss caused by reducers and
expanders.
!
Note!
The nomogram only applies to liquids of viscosity similar to water.
1.
Calculate the ratio of the diameters d/D.
2.
From the nomogram read off the pressure loss as a function of flow velocity (
downstream
from
the reduction) and the d/D ratio.
A0011907
Fig. 15:
Pressure loss due to adapters
100
10
0.5
d / D
[mbar]
0.6
0.7
0.8
0.9
1 m/s
2 m/s
3 m/s
4 m/s
5 m/s
6 m/s
7 m/s
8 m/s
1
D
d
max. 8°
Содержание Proline Promag 50
Страница 2: ......
Страница 120: ...Promag 50 Index 120 Endress Hauser ...
Страница 122: ...www endress com worldwide BA00046D 06 EN 14 11 71136623 FM SGML6 0 ProMoDo ...