Promag 50
Troubleshooting
Hauser
81
No. # 2xx
Error in DAT / no communication
251
S: COMMUNICATION I/O
$
: # 251
Internal communication fault on the amplifier board.
Replace the amplifier board.
261
S: COMMUNICATION I/O
$
: # 261
No data reception between amplifier and I/O board or
faulty internal data transfer.
Check the BUS contacts.
No. # 3xx
System limits exceeded
321
S: TOL. COIL CURR.
$
: # 321
Sensor:
Coil current is out of tolerance.
#
Warning!
Switch off power supply before manipulating the coil current
cable, coil current cable connector or measuring electronics
boards!
Remote version:
1.
Check wiring of terminals 41/42
2.
Check coil current cable connector.
Compact and remote version:
Replace measuring electronics boards if necessary
339
to
342
S: STACK CUR OUT n
!: # 339 to 342
The temporarily buffered flow portions (measuring
mode for pulsating flow) could not be cleared or output
within 60 seconds.
1.
Change the upper or lower limit setting, as applicable.
2.
Increase or reduce flow, as applicable.
Recommendations in the event of fault category = FAULT
MESSAGE (
$
)
• Configure the fault response of the output to "ACTUAL
VALUE" so that the temporary buffer can be cleared.
• Clear the temporary buffer by the measures described under
Item 1.
343
to
346
S: STACK FREQ. OUT n
!: # 343 to 346
347
to
350
S: STACK PULSE OUT n
!: # 343 to 346
The temporarily buffered flow portions (measuring
mode for pulsating flow) could not be cleared or output
within 60 seconds.
1.
Increase the setting for pulse weighting
2.
Increase the max. pulse frequency if the totalizer can handle
a higher number of pulses.
3.
Increase or reduce flow, as applicable.
Recommendations in the event of fault category = FAULT
MESSAGE (
$
)
• Configure the fault response of the output to "ACTUAL
VALUE" so that the temporary buffer can be cleared.
• Clear the temporary buffer by the measures described under
Item 1.
351
to
354
S: CURRENT RANGE n
!: # 351 to 354
Current output:
flow is out of range.
1.
Change the upper or lower limit setting, as applicable.
2.
Increase or reduce flow, as applicable.
355
to
358
S: FREQ. RANGE n
!: # 355 to 358
Frequency output:
flow is out of range.
1.
Change the upper or lower limit setting, as applicable.
2.
Increase or reduce flow, as applicable.
359
to
362
S: PULSE RANGE
!: # 359 to 362
Pulse output:
the pulse output frequency is out of range.
1.
Increase the setting for pulse weighting
2.
When selecting the pulse width, choose a value that can still
be processed by a connected counter (e.g. mechanical
counter, PLC etc.).
Determine the pulse width:
– Variant 1: Enter the minimum duration that a pulse must
be present at the connected counter to ensure its
registration.
– Variant 2: Enter the maximum (pulse) frequency as the
half "reciprocal value" that a pulse must be present at the
connected counter to ensure its registration.
Example:
The maximum input frequency of the connected counter is
10 Hz. The pulse width to be entered is:
a0004437
3.
Reduce flow.
No.
Error message / Type
Cause
Remedy (spare part
ä
86)
1
2.10 Hz
= 50 ms
Содержание Proline Promag 50
Страница 2: ......
Страница 120: ...Promag 50 Index 120 Endress Hauser ...
Страница 122: ...www endress com worldwide BA00046D 06 EN 14 11 71136623 FM SGML6 0 ProMoDo ...