11 Description of Device Functions
PROline Promag 10
114
Hauser
11.13 Group SIMULATION SYSTEM
Function description SIMULATION SYSTEM
SIMULATION FAILSAFE
MODE
Use this function to set all outputs and the totalizer to their defined failsafe
modes, in order to check whether they respond correctly. During this time, the
words "SIMULATION FAILSAFE MODE" appear on the display.
Options:
ON
OFF
Factory setting:
OFF
SIMULATION
MEASURAND
Use this function to set all outputs and the totalizer to their defined flow-
response modes, in order to check whether they respond correctly. During this
time, the words “SIMULATION MEASURAND” appear on the display.
Options:
OFF
VOLUME FLOW
Factory setting:
OFF
"
Caution!
• The measuring device cannot be used for measuring while this simulation is
in progress.
• The setting is not saved if the power supply fails.
VALUE SIMULATION
MEASURAND
!
Note!
This function is not available unless the SIMULATION MEASURAND function is
active (= VOLUME FLOW).
Use this function to specify a selectable value (e.g. 12 m
3
/s).
This value is used to test downstream devices and the flowmeter itself.
User input:
5-digit floating-point number, [unit]
Factory setting:
0 [unit]
"
Caution!
The setting is not saved if the power supply fails.
!
Note!
The appropriate unit is taken from the SYSTEM UNITS group (see Page 93)