Description of device parameters
Proline Cubemass 300 Modbus RS485
158
Hauser
Measuring mode
Navigation
Expert → Output → Double pulse out → Measuring mode (0984)
Description
Use this function to select the measuring mode for the double pulse output.
Selection
• Forward flow
• Forward/Reverse
• Reverse flow
• Rev. flow comp.
Factory setting
Forward flow
Additional information
Selection
• Forward flow
Positive flow is output, negative flow is not output.
• Forward/Reverse
Positive and negative flow are output (absolute value), but a distinction is not made
between positive and negative flow.
• Reverse flow
Negative flow is output, positive flow is not output.
• Rev. flow comp.
The flow components outside the span are buffered, balanced and output after a
maximum delay of 60 s.
For a detailed description of the options available, see the
Measuring mode
Examples
For a detailed description of the configuration examples, see the
Measuring mode
Failure mode
Navigation
Expert → Output → Double pulse out → Failure mode (0985)
Description
Use this function to select the failure mode of the double pulse output in the event of a
device alarm.
Selection
• Actual value
• No pulses
Factory setting
No pulses