Proline Promag 53 PROFIBUS DP/PA
Commissioning
Hauser
95
6.3.3
Quick Setup “Batching”
!
Note!
This function is only available when the additional “batching” software is installed in the measuring
device (order option). You can order this software from Hauser as an accessory at a later
date.
This Quick Setup menu guides you systematically through the setup procedure for all the device
functions that have to be modified and configured for batching operation. These basic settings allow
simple (one-step) batching processes.
Additional settings, e.g. for multistage batching procedures, must be made via the function matrix
itself (see the “Description of Device Functions” manual).
"
Caution!
The “Batching” Quick Setup sets certain device parameters for discontinuous measurement
operation.
If the measuring device is used for continuous flow measurement at a later time, we recommend at
you rerun the “Commissioning” and/or “Pulsating flow” Quick Setup.
!
Note!
• Before carrying out the Quick Setup “Batching” the Quick Setup “Commissioning” has to be
executed.
→
Page 89
• You can find detailed information on the batching functions in the separate “Description of Device
Functions” manual.
• You can also directly control filling process using the local display. During Quick Setup, an
appropriate dialog appears concerning the automatic display configuration. Acknowledge this by
clicking “YES”.
This assigns special batching functions (START, PRESET, etc.) to the bottom line of the display.
These can be directly executed on site using the three operating keys (
O
/
S
/
F
). Therefore,
the measuring device can be fully deployed in the field as a “batch controller”.
• You can also directly control the filling process using the fieldbus.