Micropilot M FMR244 with FOUNDATION Fieldbus
Operation
Hauser
33
5.3.3
Factory settings (Reset)
"
Caution!
A reset sets the instrument back to the factory settings. This can lead to an impairment of the
measurement. Generally, you should perform a basic setup again following a reset.
A reset is only necessary:
• if the instrument no longer functions
• if the instrument must be moved from one measuring point to another
• if the instrument is being de-installed /put into storage/installed
User input ("reset" (0A3)):
• 33333 = customer parameters (Foundation Fieldbus)
33333 = reset customer parameters
This reset is recommended whenever an instrument with an unknown 'history' is to be used in an
application:
• The Micropilot is reset to the default values.
• The customer specific tank map is not deleted.
• A linearisation is switched to "
linear
" although the table values are retained. The table can be
reactivated in the "
linearisation
"
(04)
function group.
List of functions that are affected by a reset:
The tank map can also be reset in the "
mapping
"
(055)
function of the "
extended calibr.
"
(05)
function group.
This reset is recommended whenever an instrument with an unknown 'history' is to be used in an
application or if a faulty mapping was started:
• The tank map is deleted. The mapping must be recommenced.
⇒
E HAUSER
E
+
–
• tank shape (002)
• empty calibr. (005)
• full calibr. (006)
• pipe diameter (007)
• output on alarm (010)
• output on alarm (011)
• outp. echo loss (012)
• ramp %span/min (013)
• delay time (014)
• safety distance (015)
• in safety dist. (016)
• level/ullage (040)
• linearisation (041)
• customer unit (042)
• diameter vessel (047)
• range of mapping (052)
• pres. Map dist (054)
• offset (057)
• simulation (065)
• simulation value (066)
• format display (094)
• distance unit (0C5)
• download mode (0C8)