Micropilot FMR67B HART
System integration
Hauser
35
8
System integration
8.1
Overview of device description files
• Manufacturer ID: 17 (0x0011)
• Device type ID: 0x11C1
• HART specification: 7.6
• DD files, information and files can be found at:
•
www.endress.com
•
www.fieldcommgroup.org
8.2
Measured variables via HART protocol
The following measured values are assigned to the device variables at the factory:
Device variable
Measured value
Primary variable (PV)
Level linearized
Secondary variable (SV)
Distance
Tertiary variable (TV)
Absolute echo amplitude
Quaternary variable (QV)
Relative echo amplitude
The assignment of the measured values to the device variables can be changed in the
following submenu:
Application → HART output → HART output
In a HART Multidrop loop, only one device may use the analog current value for signal
transmission. For all other devices in the
"Loop current mode" parameter
, select the
Disable
option.