Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Commissioning (block-based operation)
Hauser
85
Step
Block
Parameter
Action
5
SETUP (TRDSUP)
Empty calibration
(empty_calibration)
Enter the distance E between the
reference point R and the minimum level
(0%).
6
SETUP (TRDSUP)
Full calibration (full_calibration) Enter distance F between the minimum
(0%) and maximum (100%) level.
7
SETUP (TRDSUP)
Level (level)
Displays the measured level L.
8
SETUP (TRDSUP)
Distance (filtered_dist_val)
Displays the distance D between the
reference point R and the level L.
9
SETUP (TRDSUP)
Signal quality (signal_quality)
Displays the signal quality of the level
echo.
10
SETUP (TRDSUP)
Confirm distance
(confirm_distance)
Compare the displayed distance to the real
distance in order to start the recording of
the mapping curve.
Selection:
• 179: Manual map
• 32847: Factory map
• 32859: Distance ok
• 32860: Distance too big
• 32861: Distance too small
• 32862: Distance unknown
• 33100: Tank empty
12.6 Configuration of the on-site display
12.6.1 Factory settings of the on-site display for level measurements
Parameter
Factory setting
Format display
1 value, max. size
Value 1 display
Level linearized
Value 2 display
None
Value 3 display
None
Value 4 display
None
The on-site display can be adjusted in the
DISPLAY (TRDDISP)
transducer block.
12.7 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management
parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Conf.backup disp → Config. managem.
Block operation
Block:
DISPLAY (TRDDISP)
Parameter:
Configuration management (configuration_management)
Содержание Micropilot FMR56
Страница 197: ......
Страница 198: ...www addresses endress com 71344036 71344036 ...