Micropilot FMR51, FMR52 HART
Operating menu
Hauser
141
Damping output
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Damping out.
Description
Define time constant τ for the damping of the output current.
User entry
0.0 to 999.9 s
Factory setting
0.0 s
Additional information
Fluctuations of the measured value affect the output current with an exponential delay,
the time constant τ of which is defined in this parameter. With a small time constant the
output reacts immediately to changes of the measrued value. With a big time constant the
reaction of the output is more delayed. For τ = 0 (factory setting) there is no damping.
Failure mode
Navigation
Setup → Advanced setup → Curr.output 1 to 2 → Failure mode
Prerequisite
Current span (→ 140)
≠
Fixed current
Description
Select behavior of the output current in case of an error.
Selection
• Min.
• Max.
• Last valid value
• Actual value
• Defined value
Factory setting
Max.
Additional information
Meaning of the options
•
Min.
The current output adopts the value of the lower alarm level according to the
Current
span
•
Max.
The current output adopts the value of the upper alarm level according to the
Current
span
•
Last valid value
The current remains constant at the last value it hat before the error occurred.
•
Actual value
The output current follows the actual measured value; the error is ignored.
•
Defined value
The output current assumes the value defined in the
Failure current
parameter
The error behavior of other output channels is not influenced by these settings but is
defined in separate parameters.