Memograph CVM40
Wiring
Hauser
15
4.3
Terminal assignment
"
Caution!
If high-energy transients occur when using long signal cables, we recommend connecting a suitable
overvoltage protection (e.g. E+H HAW560/562).
Use shielded signal lines for serial interfaces!
4.3.1
Cable specification, spring terminals
All connections on the rear of the unit are designed as screw or spring terminal blocks with reverse
polarity protection. This makes the connection very quick and easy. The spring terminals are actuated
with a slotted screwdriver (size 0).
!
Note!
No ferrules need to be used when connecting flexible wires to spring terminals.
4.4
Interface connection
Ethernet, RS232/485 and USB connection
Details on connecting the interfaces can be found in the Operating Instructions on CD-ROM, Section
4.4 "Interface connection".
Wire cross-sections:
Digital I/O and analog inputs:
Power supply:
Relays:
max. 1.5 mm
2
(14 AWG) (spring terminals)
max. 2.5 mm
2
(13 AWG) (screw terminals)
max. 2.5 mm
2
(13 AWG) (spring terminals)
Stripped length:
10 mm (0.39 inch), 6 mm (0.24 inch) for power terminal