Mounting
Liquiphant FTL64
16
Hauser
1.
2.
A0042423
13
Screwing in the device
Aligning the cable entry
2.
3.
4
3.5 Nm
1.
A0042355
14
Housing with external locking screw and drip loop
The locking screw is not tightened when the device is delivered.
1. Loosen the external locking screw (maximum 1.5 turns).
2. Turn the housing, align the cable entry.
Avoid moisture in the housing, provide a loop to allow moisture to drain off.
3. Tighten the external locking screw.
5.3
Sliding sleeves
A
For more details, see the "Accessories" section.
5.4
Post-mounting check
Is the device undamaged (visual inspection)?
Does the measuring device meet the measuring point specifications?