Diagnostics and troubleshooting
Hauser
41
4. Switch on simulation and check the current output. Replace the main electronics if
the current output does not correspond to the simulated value.
11.1.4 Behavior of current output in the event of a fault
The behavior of the current output in the event of faults is defined by the
Failure behavior
current output
parameter.
Parameter overview with brief description
Parameter
Description
Selection / User entry
Failure behavior current output
Defines which current the output assumes in the case of an
error.
Min: < 3.6 mA
Max: >21.5 mA
• Min.
• Max.
Failure current
Enter current output value in alarm condition.
21.5 to 23 mA
11.2 Diagnostic information on local display
11.2.1 Diagnostic message
Measured value display and diagnostic message in alarm condition
Faults detected by the device's self-monitoring system are displayed as a diagnostic
message in alternation with the unit.
3
2
1
X X X X
X X X
X
X
X X X X
X X X
X
X
S
i
S801
A0043103
1
Status signal
2
Status symbol with diagnostic event
3
Event text
Status signals
F
"Failure (F)" option
A device error has occurred. The measured value is no longer valid.
C
"Function check (C)" option
The device is in the service mode (e.g. during a simulation).
S
"Out of specification (S)" option
The device is being operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration performed by the user (e.g. sensor frequency outside the
configured span)