Electrical connection
Liquiline System CA80CR
30
Hauser
6.2.2
Cable types
• Analog, signaling and transmission cables: e.g. LiYY 10 x 0.34 mm
2
For devices with a 24 V power supply, the terminal cross-section must be at least 2.5 mm
2
.
A current of up to 10A can flow in the case of a 24V power supply. For this reason pay
attention to the voltage drop on the supply line.The voltage at the device terminals must be
within the specified range (see "Supply voltage" section).
6.2.3
Connecting 24V devices
• To access the electronics compartment, proceed as described in the "Routing the cables"
section.
• Guide the 24V connecting cable from below through the cable gland on the inner rear panel
of the device and feed it upwards into the electronics compartment.
• Establish the connection as per