Electrical connection
Hauser
39
6.4
Connecting additional inputs and outputs
L
WARNING
Module not covered
No shock protection. Danger of electric shock!
‣
If you are modifying or extending your hardware, always fill the slots from left to right.
Do not leave any gaps.
‣
If all of the slots are not occupied: always insert a dummy cover or end cover in the slot
to the right of the last module. This ensures that the unit is shock-protected.
‣
Always ensure shock protection is guaranteed particularly in the case of relay modules
(2R, 4R, AOR).
‣
If additional shields are required, connect them with PE centrally in the control cabinet
via terminal blocks supplied by the customer.