Electrical connection

Liquicap M FMI52 HART

18

Hauser

5  

Electrical connection

Before connecting the power supply, note the following:

• the supply voltage must match the data specified on the nameplate

• switch off the supply voltage before connecting the device

• connect the potential equalization to the ground terminal on the sensor
When using the probe in hazardous areas, the relevant national standards and the

information in the safety instructions (XA) must be observed.
Use the specified cable gland only.

5.1  

Connecting requirements

5.1.1  

Potential equalization

L

DANGER

Risk of explosion!

Connect the cable screen on the sensor side only if installing the probe in Ex-areas!

Connect the potential equalization to the outer ground terminal of the housing (T13, F13,

F16, F17, F27). In the case of the stainless steel housing F15, the ground terminal can also be

located in the housing. For further safety instructions, please refer to the separate

documentation for applications in hazardous areas.

5.1.2  

Electromagnetic compatibility (EMC)

Interference emission to EN 61326, Electrical Equipment Class B. Interference immunity to

EN  61326, Annex A (Industrial) and NAMUR Recommendation NE  21 (EMC).
Failure current is in accordance with NAMUR NE43: FEI50H = 22 mA.
A standard commercial instrument cable can be used.

Information on connecting shielded cables is provided in Technical Information

TI00241F "EMC test procedures".

5.1.3  

Cable specification

Connect the electronic inserts by using commercially available instrument cables. If a potential

equalization is present, and the shielded instrument cables are used, connect the shielding on

both sides to optimize the shielding effect.

Содержание Liquicap M FMI52

Страница 1: ...Products Solutions Services Brief Operating Instructions Liquicap M FMI52 HART Capacitive Continuous level measurement for liquids KA01454F 00 EN 02 21 71510166 2021 02 01...

Страница 2: ...1 Connecting requirements 18 5 2 Wiring and connecting 20 5 3 Post connection check 23 6 Operation options 23 6 1 Overview of operation options 23 6 2 Operation via FieldCare Device Setup 28 7 Commiss...

Страница 3: ...ed to ground prior to establishing any other connections The ground terminals are located on the interior and exterior of the device Interior ground terminal protective earth is connected to the mains...

Страница 4: ...Visual inspection Operation via operating tool Write protected parameter 1 2 3 Item numbers A B C Views Hazardous area Indicates the hazardous area Safe area non hazardous area Indicates the non hazar...

Страница 5: ...m in Ex areas the appropriate national standards and regulations must be observed Separate Ex documentation which constitutes an integral part of this documentation is supplied with the device The ins...

Страница 6: ...use the Endress Hauser Operations App to scan the 2 D matrix code QR Code on the nameplate Dat IP66 IP67 NEMA4X Order Code Ser No mm Output L1 L3 L mm mm 1 2 3 4 5 6 7 9 8 10 11 12 13 14 15 A0040359...

Страница 7: ...lled in the area of the filling curtain the probe is not in contact with the container wall the distance from the container floor is 10 mm 0 39 in multiple probes are mounted next to each other at the...

Страница 8: ...then the ground connection on the probe housing must be connected to the tank using a short line The probe may not come into contact with the container wall Do not install probes in the area of the f...

Страница 9: ...HART Mounting Endress Hauser 9 The following application examples show the vertical installation for continuous level measurement A0040451 2 Rope probe A0040452 3 A probe with inactive length for the...

Страница 10: ...0 Tensioning weight with tension The end of the probe needs to be secured if the probe would otherwise touch the silo wall or another part in the tank This is what the internal thread in the probe wei...

Страница 11: ...cannot exceed 10 m 33 ft The maximum cable length between the probe and separate housing is 6 m 20 ft The required cable length must be indicated in the ordering process of a Liquicap M with separate...

Страница 12: ...4 A0040471 6 Housing side wall mounting pipe mounting and sensor side Unit of measurement mm in Values of parameters 1 Polyester housing F16 B 76 mm 2 99 in H1 172 mm 6 77 in Polyester housing F15 B 6...

Страница 13: ...eads G1 NPT1 Clamp 2 DIN 11851 flange DN50 ANSI 2 10K50 D 50 mm 1 97 in H5 89 mm 3 5 in rope probe with fully insulated inactive length D 38 mm 1 5 in H5 89 mm 3 5 in 4 2 2 Wall bracket The wall brack...

Страница 14: ...2 in 1 2 A0042318 A0042321 Screw together the wall bracket on the tube Screw the separate housing on a pipe 4 2 5 Shortening the connecting cable NOTICE Risk of damage to connections and cable Make su...

Страница 15: ...ith the pressing screw 1 2 3 22 22 34 A0042111 A0042112 A0042113 Loosen the pressing screw with an open end wrench AF22 Pull the insert seal out of the cable gland Block the adapter disk with the open...

Страница 16: ...quicap M FMI52 HART 16 Endress Hauser 7 8 9 A0042117 A0042118 A0042119 Remove the blade plug from the socket Loosen the screw to disconnect the yellow and yellow green cables Loosen the nut M4 of the...

Страница 17: ...nnecting cable To avoid the risk of short circuiting when the strands are not to be reused the connections of the new ring terminals must be insulated with a heat shrinking sleeve Use heat shrink tube...

Страница 18: ...nd terminal of the housing T13 F13 F16 F17 F27 In the case of the stainless steel housing F15 the ground terminal can also be located in the housing For further safety instructions please refer to the...

Страница 19: ...plated brass d 7 to 10 5 mm 0 28 to 0 41 in Synthetic material d 5 to 10 mm 0 2 to 0 38 in Stainless steel d 7 to 12 mm 0 28 to 0 47 in 5 1 4 Connector For the version with a connector M12 the housing...

Страница 20: ...ction Ex ia protection polyester housing F16 stainless steel housing F15 aluminum housing F17 aluminum housing F13 with gas tight process seal stainless steel housing F27 aluminum housing T13 with the...

Страница 21: ...nsert the cable 5 2 2 Terminal assignment 2 wire 4 to 20 mA with HART The twin core connecting cable is connected to the screw terminals with conductor cross section 0 5 to 2 5 mm2 20 to 13 AWG in the...

Страница 22: ...Electrical connection Liquicap M FMI52 HART 22 Endress Hauser 1 2 A B C A0040479 A Supply voltage communication resistor 250 B Commubox FXA195 C Grounding terminal...

Страница 23: ...r SIMATIC PDM 5 Commubox FXA191 RS232 or FXA195 USB 6 Transmitter If the HART communication resistor is not integrated with the supply unit a 250 communication resistor must be included in the 2 wire...

Страница 24: ...50H electronic insert 1 2 3 4 5 6 4 0 mA V V A 4 20mA 1 7 3 5 1 2 A0040485 9 FEI50H electronic insert 1 Key 2 Green LED operational status 3 Function switch 4 Red LED fault 5 Key 6 Current pick off 4...

Страница 25: ...electronics if replacing the electronic insert Red LED indicates a fault or malfunction Flashes 5x per second capacity at probe is too large short circuit at the probe or FEI50H is defective Flashes 1...

Страница 26: ...s Symbols on the display Operating mode of the device User user parameters can be edited Lock all parameters are locked Scrollbar scroll up or down to access more functions Locking state of the curren...

Страница 27: ...function 2 Due to navigating returns to the next highest menu level Increase contrast A0032710 Increases the contrast of the display module Decrease contrast A0032711 Decreases the contrast of the di...

Страница 28: ...CD ROM contact Endress Hauser DVD contact Endress Hauser 7 Commissioning The device is operated via the electronic insert the display or with FieldCare If a display is attached to the electronic inse...

Страница 29: ......

Страница 30: ......

Страница 31: ......

Страница 32: ...www addresses endress com 71510166 71510166...

Отзывы: