Levelflex M FMP43 with PROFIBUS PA
Commissioning
Hauser
59
Bypass / pipe
The "
bypass / pipe
" option is designed especially for the installation of probes in a bypass or a
stilling well. If this option is selected, the upper blocking distance is preset to 100 mm.
Coax probe (not relevant for FMP43)
Select the "
coax probe
" option when using a coaxial probe. When this setting is made, the
evaluation is adapted to the high sensitivity of the coax probe. This option should, therefore,
not
be
selected when using rope or rod probes.
Concrete wall
The "
concrete wall
" option takes into account the signal-damping property of concrete walls when
mounting with < 1 m distance to the wall.
Function "medium property" (003)
This function is used to select the dielectric constant.
Options:
•
unknown
• 1.4 to 1.6 (1.4 for installation in metallic pipes)
• 1.6 to 1.9
• 1.9 to 2.5
• 2.5 to 4.0
• 4.0 to 7.0
• > 7.0
⇒
E HAUSER
E
+
–
Media group
DC (
ε
r)
Typical liquids
Typ. measuring range
1
1.4 to 1.6
– Condensed gases, e.g. N
2
, CO
2
—
2
1.6 to 1.9
– Liquefied gas, e.g. propane
– Solvent
– Frigen / Freon
– Palm oil
4 m (354")
3
1.9 to 2.5
– Mineral oils, fuels
4
2.5 to 4
– Benzene, styrene, toluene
– Furan
– Naphthalene
5
4 to 7
– Chlorobenzene, chloroform
– Cellulose spray
– Isocyanate, aniline
6
> 7
– Aqueous solutions
– Alcohols
– Acids, alkalis
Содержание Levelflex M FMP43
Страница 4: ...Brief overview Levelflex M FMP43 with PROFIBUS PA 4 Endress Hauser...
Страница 104: ...Appendix Levelflex M FMP43 with PROFIBUS PA 104 Endress Hauser...
Страница 106: ...Levelflex M FMP43 with PROFIBUS PA Index 106 Endress Hauser...
Страница 108: ...www endress com worldwide BA358F 00 en 07 07 No 71041163 CCS FM SGML 6 0 ProMoDo 71041163...