Commissioning (via operating menu)
Levelflex FMP53 PROFIBUS PA
34
Hauser
8.
Setup → Full calibration
Enter distance F between the minimum (0%) and maximum (100%) level.
9.
Setup → Level
Displays the measured level L.
10.
Setup → Distance
Displays the distance D between the reference point R and the level L.
11.
Setup → Signal quality
Displays the signal quality of the level echo.
12.
Setup → Mapping → Confirm distance
Compare the displayed distance to the real distance in order to start the recording
of the mapping curve.
10.6 User-specific applications
For details of setting the parameters of user-specific applications, see separate
documentation:
BA01007F (Operating Instructions FMP53, PROFIBUS PA)
For the
Expert
submenu refer to:
GP01001F (Description of Device Parameters FMP5x, PROFIBUS PA)