Levelflex FMP53 PROFIBUS PA
Commissioning (via operating menu)
Hauser
33
10.5 Configuration of a level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0011360
13
Configuration parameters for level measurements in liquids
LN = Length of probe
R = Reference point of the measurement
D = Distance
E = Empty calibration (= Zero point)
L = Level
F = Full calibration (= span)
1.
Setup → Device tag
Enter tag for measuring point.
2.
Setup → Device address
Enter bus address of the device (only in case of software addressing).
3.
Setup → Distance unit
Select distance unit.
4.
Setup → Tank type
Select tank type.
5.
Setup → Tube diameter
(only if "Tank type" = "Bypass / pipe")
Enter the diameter of the bypass or stilling well.
6.
Setup → Medium group
Select medium group (
Others
or
Water based (DC >= 4)
)
7.
Setup → Empty calibration
Enter the distance E between the reference point R and the minimum level (0%).