System integration
iTHERM TrustSens TM371, TM372
22
Hauser
7.3
Supported HART
®
commands
The HART
®
protocol enables the transfer of measurement data and device data
between the HART
®
master and the field device. HART
®
masters such as the above
listed operating tools require an appropriate device driver software (DD or DTM) to
establish the data exchange. The data exchange is initiated via commands.
There are three different types of commands.
• Universal commands:
All HART
®
devices support and use universal commands. These are associated with the
following functionalities for example:
– Recognition of HART
®
devices
– Reading digital measured values
• Common practice commands:
Common practice commands offer functions which are supported and can be executed by
many but not all field devices.
• Device-specific commands:
These commands allow access to device-specific functions which are not HART
®
standard. Such commands access individual field device information.
Command No.
Designation
Universal commands
0, Cmd0
Read unique identifier
1, Cmd001
Read primary variable
2, Cmd002
Read loop current and percent of range
3, Cmd003
Read dynamic variables and loop current
6, Cmd006
Write polling address
7, Cmd007
Read loop configuration
8, Cmd008
Read dynamic variable classifications
9, Cmd009
Read device variables with status
11, Cmd011
Read unique identifier associated with TAG
12, Cmd012
Read message
13, Cmd013
Read TAG, descriptor, date
14, Cmd014
Read primary variable transducer information
15, Cmd015
Read device information
16, Cmd016
Read final assembly number
17, Cmd017
Write message
18, Cmd018
Write TAG, descriptor, date
19, Cmd019
Write final assembly number
20, Cmd020
Read long TAG (32-byte TAG)
21, Cmd021
Read unique identifier associated with long TAG
22, Cmd022
Write long TAG (32-byte TAG)
38, Cmd038
Reset configuration changed flag
48, Cmd048
Read additional device status
Common practice commands
33, Cmd033
Read device variables
34, Cmd034
Write primary variable damping value
35, Cmd035
Write primary variable range values
40, Cmd040
Enter/Exit fixed current mode