iTEMP TMT71
Operating menu and parameter description
Hauser
75
Factory setting
0,00
Sensor offset
Navigation
Application → Sensor → Sensor offset
Description
Use this function to set the zero point correction (offset) of the sensor measured value.
The value indicated is added to the measured value.
User entry
–18.0 to +18.0
Factory setting
0,0
14.2.3 Submenu: Linearization
Call./v. Dusen coeff. R0
Navigation
Application → Sensor → Linearization → Call./v. Dusen coeff. R0
Prerequisite
The RTD platinum (Callendar/Van Dusen) option is enabled in the
Sensor type
parameter.
Description
Use this function to set the R0 Value only for linearization with the Callendar/Van Dusen
polynomial.
User entry
10 to 2
000 Ω
Factory setting
100.000 Ω
Call./v. Dusen coeff. A, B and C
Navigation
Application → Sensor → Linearization → Call./v. Dusen coeff. A, B and C
Prerequisite
The RTD platinum (Callendar/Van Dusen) option is enabled in the
Sensor type
parameter.
Description
Use this function to set the coefficients for sensor linearization based on the
Callendar/Van Dusen method.
User entry
• A: 3.0e-003 to 4.0e-003
• B: -2.0e-006 to 2.0e-006
• C: -1.0e-009 to 1.0e-009
Factory setting
• A: 3.90830e-003
• B: -5.77500e-007
• C: -4.18300e-012