TMT182
6 Commissioning
Hauser
19
Commuwin II operating matrix
ƒig. 12:
:
Commuwin II operating matrix:
A = Unit functions only active on customer specific linearization
B = Unit functions only active on TC connection
C = Unit functions only active on RTD 2 wire connection
6.2.4
Configuration using HART
®
protocol and PC configuration soft-
ware ReadWin
®
2000
The configuration of the transmitter can be done using both the HART
®
protocol and the Read-
Win
®
2000 configuration software. The following table shows the structure of the interactive menu
led operation of READWIN
®
2000.
Configurable parameters (Unit function description see “Description of unit functions” on page 20)
Standard settings
– Type of sensor
– Connection mode (2-,3-, or 4-wire connection on RTD)
– Units (°C, °F or K)
– Measurement range start value
– Measurement range end value
– Coefficient X0 to X4 (on sensor type polynom RTD/TC)
– Temp.-compensation (on sensor type polynom TC)
Expanded settings
– Cold junction compensation internal/external (on TC)
– Temperature external (on TC with cold junction compensation external)
– Cable resistance compensation (on RTD 2-wire connection)
– Fault condition reaction
– Output (4 to 20 mA/20 to 4 mA)
– Damping (filter)
– Offset
– TAG (Measurement point description)
– Identifier (Descriptor)
Service functions
– Simulation (on/off)
– Reset/factory default
– Series number (only display)
– Operation code (=release code 281)