Endress+Hauser iTEMP Pt TMT180 Скачать руководство пользователя страница 4

Safety notes

TMT180

4

Hauser

1

Safety notes

Safe and secure operation of the head transmitter can only be guaranteed if the operating 
instructions and all safety notes are read, understood and followed.

1.1

Designated use

• The unit is a universal, presettable temperature head transmitter for resistance thermometer 

(RTD). The unit is constructed for mounting in a connection head (DIN form B) or field housing.

• The manufacturer cannot be held responsible for damage caused by misuse of the unit.

1.2

Installation, commissioning and operation

The unit is constructed using the most up-to-date production equipment and complies to the safety 
requirements of the local guidelines. The temperature transmitter is fully factory tested according to 
the specifications indicated on the order. However, if it is installed incorrectly or is misused, certain 
application dangers can occur. Installation, wiring and maintenance of the unit must only be done 
by trained, skilled personnel who are authorized to do so by the plant operator. This skilled staff 
must have read and understood these instructions and must follow them to the letter. The plant 
operator must make sure that the measurement system has been correctly wired to the connection 
schematics.

Electrical temperature sensors such as RTD's produce low-level signals proportional to their sensed 
temperature. The temperature transmitter converts the low-level sensor signal to a standard 4 to 20 
mA DC signal that is relatively insensitive to lead length and electrical noise. This current signal is 
then transmitted to the control room via two wires.

The transmitter electronics module is permanently sealed within the housing, resisting moisture and 
corrosive damage. Verify that the operating atmosphere of the transmitter is consistent with the 
appropriate hazardous locations certifications.

#

Warning! 
Electrical shock could cause death or serious injury. If the sensor is installed in a high voltage 
environment and a fault or installation error occurs, high voltage may be present on the transmitter 
leads and terminals.

Temperature Effects

The transmitter will operate within specifications for ambient temperatures between -40 and 
185 °F (-40 and 85 °C). Heat from the process is transferred from the thermowell to the transmitter 
housing. If the expected process temperature is near or beyond specification limits, consider the use 
of additional thermowell lagging, and extension nipple, or a remote mounting configuration to 
isolate the transmitter from the process.

Содержание iTEMP Pt TMT180

Страница 1: ...BA163R 24 ae 07 06 51006606 Operating instructions iTEMP Pt TMT180 Temperature head transmitter...

Страница 2: ...nt Please note that the manufacturer reserves the right to change and or improve the product design and specifications without notice Warning Failure to follow these installation guidelines could resu...

Страница 3: ...llation conditions 7 3 2 Installation 8 4 Wiring 10 4 1 Overview 10 4 2 Measurement unit connection 10 4 3 Potential grounding 11 4 4 Ground the Transmitter 11 5 Operation 12 5 1 Communication 12 6 Co...

Страница 4: ...e sure that the measurement system has been correctly wired to the connection schematics Electrical temperature sensors such as RTD s produce low level signals proportional to their sensed temperature...

Страница 5: ...correctly could have an indirect influence on the unit operation or could lead to an unforeseen unit reaction Caution This icon indicates activities and actions that if not followed correctly could l...

Страница 6: ...e to operate The devices comply with the applicable standards and regulations in accordance with IEC61010 Protection Measures for Electrical Equipment for Measurement Control Regulation and Laboratory...

Страница 7: ...d trademarks iTEMP and ReadWin 2000 are registered trademarks of Endress Hauser Wetzer GmbH Co KG Nesselwang Germany 3 Installation 3 1 Installation conditions When installing and operating the unit p...

Страница 8: ...ad transmitter in the connection head in such a way that the current output terminals terminal 1 and 2 are towards the cable entry gland Pos 7 Fix the head transmitter Pos 4 and sensor inset Pos 5 int...

Страница 9: ...the transmitter housing Pos 4 using a screwdriver Max torque pound feet 1 Nm Feed the sensor inset cables through the conduit of the transmitter housing and the central hole in the head transmitter At...

Страница 10: ...talled we recommend grounding it via one of the ground screws Sensors Connect the sensor cables to the respective head transmitter terminals Terminals 3 to 6 by following the wiring diagram see Fig 6...

Страница 11: ...eld to the special EMC cable gland 4 4 Ground the Transmitter The transmitter will operate with the current signal loop either floating or grounded However the extra noise in floating systems affects...

Страница 12: ...tor of the interface connecting cable to the SETUP socket in the head transmitter see Fig 7 in Chapter 4 2 2 Connect the RS232C connector to a free serial interface socket or the USB connector to a fr...

Страница 13: ...int documentation The head transmitter left the factory with a default parameter configuration If no customer specific configuration was mentioned on the order then the default parameter configuration...

Страница 14: ...asurement range start value Input of 4 mA value Input Limitation values see Sensor type 0 C Measurement range end value Input of 20 mA value Input Limitation values see Sensor type 100 C Coefficient X...

Страница 15: ...se with a temperature head transmitter or consult the factory for a replacement special sensor or transmitter combination 8 Accessories Service functions Output simulation Activate simulation mode Inp...

Страница 16: ...ction cure Fault current 3 6 mA or 21 mA Defective sensor Check sensor Incorrect connection of RTD Connect cables correctly to terminal schematic Incorrect connection of the 2 wire cable Connect cable...

Страница 17: ...of the local disposal regulations 9 6 Software history Head transmitter installation set For European Style installation 8 screws 8 springs 8 E rings For U S Style installation 8 machine screws M4x20...

Страница 18: ...0 3 Output Output signal Analog 4 to 20 mA 20 to 4 mA Breakdown information Breakdown information to NAMUR NE 43 Breakdown information is created when the measuring information is invalid or not prese...

Страница 19: ...Calibration temperature 77 F 9 F 25 C 5 C Maximum measured error Influence of supply voltage 0 01 V deviation from 24 V Percentages refer to the full scale value Influence of ambient temperature Temp...

Страница 20: ...ensation allowed Degree of protection IP 00 NEMA 4 IP 66 installed in field housing TAF 10 Shock and vibration resistance 4g 2 to 150 Hz as per IEC 60 068 2 6 Electromagnetic compatibility EMC CE Elec...

Страница 21: ...tly on the transmitter to prevent from manipulation The device parameters of the head transmitter are configured using the PC operating software ReadWin 2000 Remote operation Configuration set Configu...

Страница 22: ...p building approval Germanischer Lloyd CSA GP CSA General Purpose Other standards and guidelines IEC 60529 Degrees of protection by housing IP Code IEC 61010 Safety requirements for electrical measure...

Страница 23: ...hecklists 16 Function check Measurement range excess 13 Measurement range undercut 13 Sensor short circuit 13 Function group 14 G GL approval 6 I Installation angle 7 Installation check 13 Installatio...

Страница 24: ...ress com Endress Hauser Canada 1075 Sutton Drive Burlington ON L7L 5Z8 Tel 905 681 9292 800 668 3199 FAX 905 681 9444 www ca endress com Endress Hauser Mexico S A de C V Av Gustavo Baz No 43 Fracc Bos...

Отзывы: