TMT180
Commissioning
Hauser
13
6
Commissioning
6.1
Installation and function check
Installation check
Monitor all connections making sure they are tight. In order to guarantee fault-free operation, the
terminal screws must be screwed tightly onto the connection cables.
Function check
Measuring the analog 4 to 20 mA output signal or following failure signals:
6.2
Switch on the device
Once the power supply has been connected, the head transmitter is operational.
6.3
Configuration
6.3.1
Setting up using the PC configuration software
The operating and readout software is an universally applicable service and configuration software.
The operating software offers the user the following possibilities:
• Set-up device functions
• Measured value visualization
• Device parameter data storage
• Measuring point documentation
The head transmitter left the factory with a default parameter configuration. If no customer specific
configuration was mentioned on the order then the default parameter configuration is constructed
as follows:
!
Note!
If a change has been made to the measurement point then, head transmitter can be re-configured.
In order to re-configure the parameters follow these instructions:
• Install the configuration software and make connection to the PC (see Chap. 5, ’Operation’).
• For detailed operating instructions for the PC configuration software please read the online
documentation (
BA137R/09/ae
) contained in the PC operation and readout software (see
folder ’
Doc
’).
This software can be downloaded free of charge from the Internet at the following address:
www.readwin2000.com
Measurement range undercut
linear fall to 3.8 mA
Measurement range excess
linear rise to 20.5 mA
Sensor break; sensor short circuit
≤
3.6 mA or
≥
21.0 mA
Sensor
Pt100 (RTD)
Connection mode
3-wire
Measuring range and units
0 to +100 °C